CX Series Power Conditioning Transformer (2-10kVA)
/images/productimages/Oneac/cx-series-conditioner.jpg
/images/productimages/Oneac/cx-series-conditioner-inside.jpg
CX Series Power Conditioning Transformer (2-10kVA)
Manufacturer:  Oneac
  PDF document Available
ONEAC CX Series Power Conditioning Transformer in NEMA enclosure with disconnect (2 - 10 kVA):Reliable operation of manufacturing control systems is critical despite the harsh electrical environment in which they must operate. ONEAC CX Series power-conditioning transformers protect critical equipment from power disturbances and provide other key power functions.
Model:
2 kVA, 3.6kVA, 5kVA, 7.2kVA, 9.6kVA

See PDF document for specifications
Characteristics:
-Nominal input Voltage: 240, 480 VAC; 60 Hz

-Surge voltage withstand capability: ANSI/IEEE C62.41 Category A&B,
 6 kV/200 & 500 Amp, 100 kHz ringwave

-Surge and Noise Rejection-Isolation: with unit under power, and ANSI/IEEE C62.41  Category A pulse applied either normal mode (L-N) or common  mode (N-G) at the input,  the noise output voltage will be less than 10V normal mode and less than 0.5V common  mode in all four quadrants using a Keytek 711A/J (or equivalent) surge generator and a  low-voltage, high sensitivity probe.

-Load Power Factor: 0.3 leading to 0.3 lagging

-Load Regulation Response Time: <2 msec for a 50% change in load

-Interruption Response Time: output voltage will track input voltage in less than 2 msec  at power-off and power-on for a single-cycle asynchronous notch
-Distortion: <1% THD added into a resistive load

-Overload Protection: fuse

-Cooling: convection