Rayvoss 240-3Y-M3-4-06-B
Transient Voltage Surge Suppression Systems
|
|
|
The Rayvoss 240-3Y-M3-4-06-B is suitable to protect on 240/415V three phase wye (4-wire plus ground) electrical installations. The system includes four Metal Oxide Varistor (MOV) based Strikesorb-40 protection modules.
|
Model:
Rayvoss 240-3Y-M3-4-06-B
See PDF document for specifications.
Specifications:
-Nominal Voltage 240/415V, Three Phase Wye
-Maximum Continuous Operating Voltage (MCOV, L -N) 300V
-Maximum Surge Current IMAX (8/20) NEMA LS1 (L-G) 140kA
-Maximum Lightning Current IIMP (10/350) IEC 61643-1 (L-G) 7.5kA
-Short Circuit Current Rating (SCCR) 100kAIC
-Long Duration Surge Performance
-500A square waveform 2ms (IEEE C62.11) 250 hits
-Response Time < 1ns
-Operating Temperature -40…+85°C
-Environmental Protection IP65 – NEMA 4
-Enclosure Dimensions 12” x 10” x 6”
-Warranty 10 years