Sinergy S II Series UPS (700VA-3000VA)
|
|
|
Protecting key electronic equipment from power disruptions will make a positive financial impact on your business systems. The Sinergy S II Series Uninterruptible Power Supply (UPS) provides online double conversion technology to handle inconsistencies in the electrical system, to make brief power disruptions harmless, and to provide battery back-up to bridge prolonged power outages.
|
Model:
S0K7XAU
S1K0XAU
S1K5XAU
S2K0XAU
S3K0XAU
S2K0XHU
S3K0XHU
See PDF document for specifications
Characteristics:
-Nominal input voltage: XAU models (low voltage): 120 V (factory default)
100, 127 V (selectable)
-XHU models (high voltage): 208 V (factory default) 200, 208, 220, 230, 240 V (selectable)
-Available output voltage: XAU models (low voltage): 120 V (factory default) 100, 127 V (selectable)
-XHU models (high voltage): 208 V (factory default) 200, 208, 220, 230, 240 V (selectable)
-Surge voltage withstand capability: ANSI/IEEE C62.41 Cat. A & B
-Crest factor: 3:1
-Principle of operation: online, double conversion
-Alarms: Mains power loss, low battery, overload, on bypass
-Battery test: automatic, once per month (adjustable through UPS management software supplied)
-Battery management: EXB auto recognition, automatic runtime adjustment, protection against deep discharge
-Recharge time to 90% available capacity: 5 - 8 hours (internal batteries)
-Relative humidity: 20-90%, no condensationGMT
-Frequency: 50/60 Hz, auto-select, input frequency range 40-70 Hz
-Input frequency tolerance: ± 5%
-Frequency tolerance, normal operation: Output frequency synchronized with mains frequency
-Frequency tolerance, power failure: ± 0.5% (internal frequency generator)
-Total harmonic distortion (linear load): <4%
-Automatic bypass: integrated
-Output waveform: sinusoidal
-Overload capacity: 110% warning; 110-130%: 12 seconds, switches to bypass; >130% 1.5 seconds, switches to bypass (contact technical service for details)
-Port: (1) serial, (1) USB standard
-COM slot: (1) for SNMP/web interface
-RPO: standard
-Operational temperature: 50°F to 77°F (+10°C to +25°C) (for integrated batteries)
-EMC: 700-1500 VA models: FCC part 15, class B; EN 61000-6-1; EN 61000-602; EN 55024
-2000-3000 VA models: FCC part 15, class A; EN 61000-6-1; EN 61000-602; EN 55024