Rayvoss 120-2S-N3-2-06-A
AC Transient Voltage Surge Suppression Systems
|
|
|
The Rayvoss 120-2S-N3-2-06-A is suitable to protect a 120/240V split phase (3 wire plus ground) electrical installation. The system includes two Metal Oxide Varistor (MOV) based Strikesorb-40 protection modules.
|
Model:
Rayvoss 120-2S-N3-2-06-A
See PDF document for specifications.
Specifications:
-Nominal Voltage 120/240V Split Phase Maximum
-Continuous Operating Voltage (MCOV) 150V
-Maximum Surge Current IMAX (8/20) NEMA LS1 (L-G) 140kA
-Maximum Lightning Current IIMP (10/350) IEC 61643-1 (L-G) 7.5kA
-Let Through Voltage Level for surge current 10kA* (8/20) (L-G) 435V
-Short Circuit Current Rating (SCCR) 200kAIC
-Long Duration Surge Performance 500A square waveform 2ms (IEEE C62.11) 250 hits
-Response Time < 1ns
-Operating Temperature -40…+85°C
-Environmental Protection IP65 – NEMA 4
-Enclosure Dimensions 20” x 16” x 8”
-Warranty 10 years