Total Protection Solutions
I-Sense
I-Sense
Manufacturer:  SoftSwitching
  PDF document Available
-I-Grid uses ultra-low cost I-Sense™ monitors to capture and transmit power data through the Internet to a central server for display on the I-Grid website, as well as send event notification to monitor owners.
-The I-Grid eliminates the need for expensive hardware and software, reducing the cost of power monitoring from as much as $15,000 to under $750 per monitor.
Specifications:
See PDF document for more specifications.

Input Voltage Range: 0 to 120% of nominal voltage
Accuracy of Measurement: Typically +/- 0.2% of full scale
Maximum +/- 1% of full scale
True RMS computation
Sampling Rate: 32 times per cycle for each phase (3X oversampling)
Event Detection Criteria: RMS voltage deviation < 87% or > 115% of nominal. Adaptive wave shape deviation algorithm
Data Logging: Non-volatile memory event storage
Up to 200 events for single phase units
Up to 70 events for three phase units
Periodic min/max RMS voltage data over user-selected periods
User configurable event dial-up criteria
Protocols: V.32bis (14,400 bps) / V.42 Error Correction
HTTP, TCP/IP, PPP, XML
Shared touch-tone analog telephone line compatible
Recommend maximum of three shared units per telephone line
Currently available for use in USA
User Interface: LED/Button
Internal Battery: Rechargeable, long life, 9 volt
Enables dial-up on sustained power interruption
Temperature Range: 0° C to 45° C
Certification: UL, FCC, CSA, CE, ICES
Diagnostics: Flashing LED for response/event notification