Total Protection Solutions
CX Series Power Conditioning Transformer (75-1000VA)
/images/productimages/Oneac/cx-series-conditioner2.jpg
/images/productimages/Oneac/cx-series-conditioner2-inside.jpg
CX Series Power Conditioning Transformer (75-1000VA)
Manufacturer:  Oneac
  PDF document Available
Reliable operation of manufacturing control systems is critical despite the harsh electrical environment in which they must operate. ONEAC CX Series power-conditioning transformers protect critical equipment from power disturbances and provide other key power functions.
Model:
CX140
CX250
CX500
CX750
CX1000

See PDF document for specifications
Characteristics:
-Nominal Input Voltage: 120, 240, 480 Vac, 50/60 Hz

-Surge Voltage Withstand Capability: ANSI/IEEE C62.41 Category A&B,
 6 kV/200 & 500 Amp, 100 kHz ringwave Surge and Noise Rejection-Isolation: with unit  under power, and ANSI/IEEE C62.41 Category A pulse applied either normal mode (L-N) or  common mode (N-G) at the input, the noise output voltage will be less than 10V normal  mode and less than 0.5V common  mode in all four quadrants using a Keytek 711A/J (or  equivalent) surge generator and a low-voltage, high sensitivity probe.

-Load Power Factor: 0:3 leading to 0.3 lagging

-Load Regulation Response Time: <2 msec for a 50% change in load

-Interruption Response Time: output voltage will track input voltage in less
 than 2 msec at power-off and power-on for a single-cycle asynchronous notch

-Distortion: <1% THD added into a resistive load

-Overload Protection: fuse

-Cooling: convection

-RF½ Insertion Loss (line to load and load to line)
 400 kHz to 4 MHz — 50 dB typical
 100 kHz to 10 MHz — 40 dB typical
 30 kHz to 30 MHz — 30 dB typical