CX Series Power Conditioning Transformer (75-1000VA)
|
|
|
|
Reliable operation
of manufacturing control systems is critical despite the harsh electrical environment in which they must
operate. ONEAC CX Series power-conditioning transformers protect critical equipment from power
disturbances and provide other key power functions.
|
Model:
CX140
CX250
CX500
CX750
CX1000
See PDF document for specifications
Characteristics:
-Nominal Input Voltage: 120, 240, 480 Vac, 50/60 Hz
-Surge Voltage Withstand Capability: ANSI/IEEE C62.41 Category A&B,
6 kV/200 & 500 Amp, 100 kHz ringwave Surge and Noise Rejection-Isolation: with unit under power, and ANSI/IEEE C62.41 Category A pulse applied either normal mode (L-N) or common mode (N-G) at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants using a Keytek 711A/J (or equivalent) surge generator and a low-voltage, high sensitivity probe.
-Load Power Factor: 0:3 leading to 0.3 lagging
-Load Regulation Response Time: <2 msec for a 50% change in load
-Interruption Response Time: output voltage will track input voltage in less
than 2 msec at power-off and power-on for a single-cycle asynchronous notch
-Distortion: <1% THD added into a resistive load
-Overload Protection: fuse
-Cooling: convection
-RF½ Insertion Loss (line to load and load to line)
400 kHz to 4 MHz — 50 dB typical
100 kHz to 10 MHz — 40 dB typical
30 kHz to 30 MHz — 30 dB typical