CX Series Power Conditioner in NEMA (1100-5160VA)
|
|
|
|
Reliable operation of manufacturing control systems is critical despite the harsh electrical environment in which they must operate. ONEAC CX Series power-conditioning transformers protect critical equipment from power disturbances and provide other key power functions.
|
Model:
CX500N
CX750N
CX1000N
See PDF document for specifications
Characteristics:
-Nominal input Voltage: 120, 240, 480 Vac, 50/60 Hz
-Surge voltage withstand capability: ANSI/IEEE C62.41 Category A&B,
6 kV/200 & 500 Amp, 100 kHz ringwave
-Surge and Noise Rejection-Isolation: with unit under power, and ANSI/IEEE
C62.41 Category A pulse applied either normal mode (L-N) or common mode
(N-G) at the input, the noise output voltage will be less than 10V normal mode
and less than 0.5V common mode in all four quadrants using a Keytek 711A/J
(or equivalent) surge generator and a low-voltage, high sensitivity probe.
-Load Power Factor: 0:3 leading to 0.3 lagging
-Load Regulation Response Time: <2 msec for a 50% change in load
-Interruption Response Time: output voltage will track input voltage in less
than 2 msec at power-off and power-on for a single-cycle asynchronous notch
-Distortion: <1% THD added into a resistive load
-Overload Protection: fuse
-Cooling: convection